| 10-667 |
Hyperon Power System - PDS 4203 |
|
Download C&D Technologies Specification
Sheet |
|
Hyperon is a -48 Vdc, up to 10,800 Adc system that supplies a complete
solution for central offices, MTSO's, Data centers, Gateway switching centers, regional switching
centers and any other -48Vdc high power applications. It features internal bay to bay buswork,
welded frame structure, Series 100 controller and C&D's unique cable trough providing extra
cabling space for ease of installing and maintenance. (Note: The PDF alone can supply up to 6,000
amps of distribution. However, maximum distribution for the system (PDF/SDF's combined) is
rated for 10,800 Amps) |
|
|
|
|
|
|
|
|
Basic List Configurations |
| 110.4203L.1J |
Hyperon 6,000 amp rated PDF (Primary Distribution Frame) with an
integrated 10,800 amp bay to bay bus structure, supporting up to 18 TPL
fuses, expandable to 54, utilizing the Series 100 controller. (List 1
includes the required splice kit from the PDF to the Rectifier bay) |
| 110.4203L.3J |
Hyperon 6,000 amp rated PDF (Primary Distribution Frame) & 6,000 amp
rated SDF (Supplemental Distribution Frame) with an integrated 10,800
amp bay to bay bus structure supporting up to 36 TPL fuses, expandable
to 54, utilizing the Series 100 controller. (List 3 system includes the
required splice kit from the PDF to the Rectifier bay and the PDF to the
SDF) |
|
|
|
List A: (SDF) Supplemental Distribution Frames |
| 4203L.A1 |
Hyperon 6,000 amp rated SDF (Supplemental Distribution Frame) is used
with List 1 or 3, the SDF is mechanically identical to the PDF
(110.4203L.1 or L.3), except the controller is not required. (with List
1, MAX is 2 SDF; with List 3 MAX is 1 SDF; List A1 includes the required
splice kit from the SDF to the next SDF) |
|
|
|
List B & C: Rectifier Bay and Rectifier Options |
| 4203L.B1 |
Hyperon 1,200 amp rated rectifier bay, with an integrated 10,800 amp bay
to bay bus structure supporting up to 6 -48 volt 200amp switchmode
rectifiers, expandable to 54. Utilizes splice plates to connect to the
PDF & SDF. The integrated bus includes landings for up to four battery
strings. (List B1 includes the required splice kit from Rectifier bay to
Rectifier bay) |
| 4203L.C1 |
Hyperon -48volt, 200 amp switchmode rectifiers, up to (6) per rectifier
bay. |
|
|
|
List D: PDF & SDF Primary Distribution Options |
| 4203L.D1 |
Hyperon 2,400 amp rated TPL distribution panels are designed for the
Hyperon PDF and SDF distribution frames. Supports up to (6) TPL fuses
ranging from 200-600 amps. includes individual shunts per fuse, a front
access door to the load cable landings, supporting up to two 1000MCM
lugs per position (option available for (4) landings). GMT fuse for FA
detection with individual LED's. Order up to (3) distribution panels per
PDF or SDF frame. |
|
|
|
List E & F: BDFB (Battery Distribution Fuse Bay) Options |
|
|
| 10-668 |
Hyperon BDFB - Battery Distribution Fuse Bay |
|
Download C&D Technologies Specification
Sheet |
|
The BDFB is the secondary distribution feed from the PDF & SDF frames to
power the customers equipment. |
|
The BDFB bays are stand-alone equipment with their own monitoring
options, generally located at the end |
|
of the equipment line ups. Available in 2, 4 or 6 sections per bays.
Distribution options include AM1 breakers |
|
or TPS fuses. A & B feeds, 24 positions per section for a total of 144
positions per BDFB. Order up to (3) |
|
distribution panels per BDFB frame. |
|
|
|
List E : BDFB (Battery Distribution Fuse Bay) Options |
| 4203L.E1 |
Hyperon BDFB bay supports up to (3) distribution panels, includes the
Series 10 simple monitor, FA detection with individual LED's for the
BDFB bay and GMT fuse panels that are feed by the BDFB bay, an audible
alarm for BDFB FA alarm, output relays FA's to feed back to the PDF
frame. input/output connections for daisy chaining the BDFB and GMT fuse
alarms. cable routing brackets to support the input cables. (Top feed) |
| 4203L.E3 |
Hyperon BDFB bay supports up to (3) distribution panels, includes the
Series 10 simple monitor, FA detection with individual LED's for the
BDFB bay and GMT fuse panels that are feed by the BDFB bay, an audible
alarm for BDFB FA alarm, output relays FA's to feed back to the PDF
frame. input/output connections for daisy chaining the BDFB and GMT fuse
alarms. cable routing brackets to support the input cables. (Bottom
feed) |
| 4203L.E2 |
Hyperon BDFB bay Same as 4203L.E1 but includes the Series 200 monitor
with enhanced features, monitors A & B feeder shunts, voltage and busbar
temperatures on each distribution panel, Major and Minor alarm outputs,
LCD display, audible alarm, programmable thresholds, auto-detection
panel. (Top feed) |
| 4203L.E4 |
Hyperon BDFB bay Same as 4203L.E3 but includes the Series 200 monitor
with enhanced features, monitors A & B feeder shunts, voltage and busbar
temperatures on each distribution panel, Major and Minor alarm outputs,
LCD display, audible alarm, programmable thresholds, auto-detection
panel. (Bottom feed) |
|
|
|
List F: BDFB Distribution Options |
| 4203L.F1 |
Hyperon 1,200 amp rated AM1 distribution panels are designed for the
Hyperon BDFB frames. Supports up to (24) AM1 breakers per section, for a
total of (48) per panel, ranging from 5-100 amps. includes individual
shunts per section. A front access door allows for installation of
bolt-in breaker kits. The panel also includes FA indicators for A & B
sections, ground return landings that are paired with the loads and an
option for lockable doors. Order up to (3) distribution panels per BDFB
frame. |
| 4203L.F2 |
Hyperon 1,200 amp rated TPS distribution panels are designed for the
Hyperon BDFB frames. Supports up to (24) TPS fuses per section, for a
total of (48) per panel, ranging from 3-70 amps. Includes individual
shunts per section. A front access door allows for installation of the
fuse. The panel also includes FA indicators for A & B sections, ground
return landings that are paired with the loads and an option for
lockable doors. Order up to (3) distribution panels per BDFB frame.
(Includes 48 fuse blocks) |
|
|
|
List G: Co-Location Distribution Options |
| 4203L.G1 |
Hyperon Co-Location distribution panel is a general purpose 500 amp
rated AM1 distribution panel, mounts in a 23" relay rack. Supports up to
(10) AM1 breakers per section, for a total of (20) per panel, ranging
from 5-100 amps. Includes individual shunts per section. A front access
door allows for installation of bolt-in breaker kits and access to the
ground returns. The panel includes FA indicators for A & B sections,
ground return bus, digital meter for voltage, current and wattage usage,
hi current thresholds. supports 2-hole lugs for loads and returns |
|
|
|
Miscellaneous Accessories |
| 385.5833.00 |
Hyperon bus adapter, allows for (4) each 535 up to 1,000 MCM cable
connections to a single TPL fuse output. Order (1) kit per fuse position
requiring (4) cable connections. |
| 385.5834.00 |
Hyperon BDFB bus adapter kit, provides strapping to interconnect BDFB
distribution panels for increased distribution positions from a single
feed . Order (1) kit to join two List F distribution panels. |
| 385.2977.00 |
Seismic anchor kits, provides "Hilti" anchors and shims Zone 2 seismic
mounting kit |
| 385.2978.00 |
Seismic anchor kits, provides "Hilti" anchors and shims Zone 3 seismic
mounting kit |
| 385.2979.00 |
Seismic anchor kits, provides "Hilti" anchors and shims Zone 4 seismic
mounting kit |
|
|
|
Bay Isolation Kits: Provides the necessary hardware to electrically
isolate the bay from extraneous frame ground due to contact with floor
or mounting hardware. (order (1) kit per each bay/bay type ordered) |
| 385.5820.00 |
Hyperon PDF/SDF Bay isolation kit, includes anchors and isolation pad. |
| 385.5822.00 |
Hyperon Rectifier Bay isolation kit, includes anchors and isolation pad. |
| 385.5836.00 |
Hyperon BDFB Bay isolation kit, includes anchors and isolation pad. |
|
|
|
Fuse and Breaker Options: |
|
TPS Fuses for 4203L.F2 (BDFB TPS Fuse Panel) |
| 280-1413-00 |
TPS Fuse 3 ampere |
| 280-1414-00 |
TPS Fuse 5 ampere |
| 280-1416-00 |
TPS Fuse 6 ampere |
| 280-1419-00 |
TPS Fuse 10 ampere |
| 280-1422-00 |
TPS Fuse 15 ampere |
| 280-1425-00 |
TPS Fuse 20 ampere |
| 280-1428-00 |
TPS Fuse 25 ampere |
| 280-1431-00 |
TPS Fuse 30 ampere |
| 280-1433-00 |
TPS Fuse 40 ampere |
| 280-1436-00 |
TPS Fuse 50 ampere |
| 280-1439-00 |
TPS Fuse 60 ampere |
| 280-1442-00 |
TPS Fuse 70 ampere |
|
|
|
Breaker Options: |
|
TPL Fuses for 4203L.D1 (PDF/SDF TPL Fuse Panels) |
| 280-1388-00 |
TPL Fuse 200 ampere |
| 280-1391-00 |
TPL Fuse 225 ampere |
| 280-1394-00 |
TPL Fuse 250 ampere |
| 280-1397-00 |
TPL Fuse 300 ampere |
| 280-1400-00 |
TPL Fuse 400 ampere |
| 280-1403-00 |
TPL Fuse 500 ampere |
| 280-1407-00 |
TPL Fuse 600 ampere |
|
|
|
AM1 Bolt-in Breakers for 4203L.F1 (BDFB AM1 Breaker Panel) |
| 274-3800-05 |
5-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-10 |
10-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-15 |
15-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-20 |
20-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-25 |
25-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-30 |
30-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-40 |
40-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-50 |
50-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-60 |
60-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-70 |
70-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-80 |
80-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-3800-100 |
100-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
|
|
|
AM1 Breakers for 4203L.G1 (Co-Location distribution Panels) |
| 274-2920-05 |
5-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-10 |
10-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-15 |
15-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-20 |
20-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-25 |
25-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-30 |
30-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-40 |
40-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-50 |
50-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-60 |
60-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-70 |
70-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-80 |
80-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 274-2920-100 |
100-ampere AM1 type circuit breaker kit for panels with alarm switch, 1
position |
| 213-3923-00 |
Cover for 1 unused AM1 breaker position, plastic(add covers required to
fill empty slots) |